13.1.2 三相或单相的交流单芯电缆,不得单独穿于钢导管内。 16.1.1 金属电缆桥架及支架和引入或引出的金属电缆导管必须接地(PE)或接零(PEN)可靠,且必须符合下列规定: 1 金属电缆桥架及其支架全长不应少于2处与接地(PE)或接零(PEN)干线相连接。 2 非镀锌金属电缆桥架间连接板的两端应跨接铜芯接地线,接地线最小允许截面积不小于4mm。 3 镀锌电缆桥架间连接板的两端不跨接接地线,但连接板两端不少于2个有防松螺帽或防松垫圈的连接固定螺栓。 20.1.1 金属的导管和线槽必须接地(PE)或接零(PEN)可靠,并符合下列规定: 1 可挠性导管、金属线槽和明配的镀锌钢导管